Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM00006
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/30/2007 | ELECTRIC - INTERMEDIATE | Approved | ||
04/24/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO TILE |
|
03/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK STUD FRAMED WALL 1. FINISH VDV CABLING 2. PVC CONDUITS NOT ALLOWED IN A PLENUM 300.22 |
|
03/26/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PROPERLY SECURE M/C CABLE AND FLEX CONDUIT. PROTECT INSIDE OF STUD CHANNELS, ALSO AT TOP PLATES, STUDS-ABOVE CEILING PER 330.30 AND 300.11 2) SECURE CONDUIT SUPPORTS 3) FILL UNUSED OPENING 4) VDV CABELING TO BE PER 725.3 & 6, 760.3 & 6 AND 800.3 & 6 5) PLEASE VERIFY BOXES ARE RATED FOR BODNING AT 277V 250.97 |
|
03/23/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |