Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/30/2007 ELECTRIC - INTERMEDIATE Approved
04/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO TILE
03/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK STUD FRAMED WALL
1. FINISH VDV CABLING
2. PVC CONDUITS NOT ALLOWED IN A PLENUM 300.22
03/26/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PROPERLY SECURE M/C CABLE AND FLEX CONDUIT. PROTECT INSIDE OF STUD CHANNELS, ALSO AT TOP PLATES, STUDS-ABOVE CEILING PER 330.30 AND 300.11
2) SECURE CONDUIT SUPPORTS
3) FILL UNUSED OPENING
4) VDV CABELING TO BE PER 725.3 & 6, 760.3 & 6 AND 800.3 & 6
5) PLEASE VERIFY BOXES ARE RATED FOR BODNING AT 277V 250.97
03/23/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*