Permit: T07BU02680

Parcel: 141150640


Addresses:

7944 S TEABERRY AV

Inspection Status: Approved

Inspection History: POOL/SPA PRE-GUNITE

Date Description Inspector Results Comments
02/19/2008 POOL/SPA PRE-GUNITE Approved IVRS - Inspection :*
02/12/2008 POOL/SPA PRE-GUNITE Partial Approval IVRS - Inspection :*
1) DON'T USE ACORN TYPE BONDING CLAMPS, USE ALL BRASS TO ISOLATE COPPER FROM STEEL
2) NEED 4 PIG TAILS #8 COPPER ON EACH SIDE OF POOL, TO BE BURRIED UNDER KOOL DECK, THEY WILL BE ATTACHED TO A #8 COPPER RUN THE CIRCUMFRANCE OF POOL. THIS LOOP WILL NEED TO BE INSPECTED BEFORE KOOL DECK IS POURED
3) YOU WILL NEED TO BOND METAL FENCE 5'-0" OR CLOSER TO H20 EDGE