Permit: T07BU02671

Parcel: 12218257A


Addresses:

3719 E SPEEDWAY BL

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/12/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
DO NOT SCHEDULE ANY INSPECTION UNTIL ALL CORRECTIONS HAVE BEEN MADE FROM PREVIOUS INSPECTION. PROVIDE A MECHANICAL PERMIT FOR ALL WORK ON THE EXHAUST SYSTEM. A REINSPECTION FEE WILL BE CHARGED IF WORK IS NOT COMPLETE AT NEXT INSPECTION.
01/23/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- THE HOOD & GREASE DUCT UP TO THE ROOF ARE APPROVED FOR TYPE 1 USE.
- HOWEVER, THE DUCTING ON ROOF CONNECTING TO THE EXHAUST FAN ARE NOT RATED FOR TYPE 1 USE
- THE EXHAUST FAN IS APPROVED FOR TYPE 1 USE BUT NEEDS A GREASE COLLECTOR UNDER THE FAN
- THE DISCHARGE MUST TERMINATE ABOVE THE UPPER ROOF
- CLEAN ALL GREASE OFF OF THE ROOF AROUND THE FAN AND INSTALL THE GREASE COLLECTOR
- MAKE UP AIR DOES NOT WORK & MUST BE INTERLOCKED WITH THE EXHAUST FAN
- THERE IS NO WAY TO CHECK THE FIRE RATED SHAFT OR FIRE WRAP AROUND GREASE DUCT DUE TO CONCEALED SPACE
- WHY IS GREASE LEAKING ONTO THE FRONT OF THE HOOD FROM THE EXHAUST DUCT?
- NEED TO SEE DUCT CONNECTION TO TOP OF HOOD
- HIRE A QUALIFIED MECHANICAL CONTRACTOR TO DO THE WORK AND PROVIDE A MECHANICAL PERMIT FOR WORK.