Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/08/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE APPLY FOR A MECHANICAL PERMIT FOR REPLACEMENT OF TYPE 1 REQUIREMENT ON ROOF NO LATER THAN APRIL 18, 2008 PERMIT MUST BE OBTAINED NO LATER THAN MAY 16, 2008 ALL WORK TO BE COMPLETED BY JUNE 6, 2008 (SIGNED BY JESSE SANDERS) |
|
| 03/19/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* - SEE NOTES FROM PREVIOUS INSPECTION - PROVIDE A MECHANICAL PERMIT & APPROVED PLANS FOR REPLACEMENT OF EXHAUST EQUIPMENT - INTERLOCK MAKE UP AIR WITH EXHAUST FANS - DUCTS ON ROOF NOT APPROVED FOR TYPE I - PROVIDE INSTALL INSTRUCTIONS FOR CLEANOUT DOORS |
|
| 12/28/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - BLOWERS NOT APPROVED FOR TYPE 1 HOODS STANDARD DUT BLOWERS NOT APPROVED FOR GREASE LADEN EXHAUST - POWER TO MAKE UP AIR DISCONNECTED - CLEANOUT DOORS ON GREASE DUCT NOT APPROVED - GREASE DUCT WITHIN 18" OF COMBUSTIBLE MATERIAL |