Inspection History Details
Inspection Status: Approved
Inspection History: GRADING - FINAL
Permit Number - T07BU02618
Inspection Description - GRADING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2009 | GRADING - FINAL | Approved | Received as-builts and fielded checked, returned to Laith, OK | |
06/08/2009 | GRADING - FINAL | Partial Approval | received engineers cert for site and drainage. | |
06/05/2009 | GRADING - FINAL | Partial Approval | Checked site after Clinker Tack applied, looks very good, still need as-builts and engineers cert. for dainage | |
04/01/2009 | GRADING - FINAL | Denied | Checked as-builts and looked at site for final grading. Final grading punch list; 1) Install bollards in dumpster enclosure per detail 15 sht. 2 2) Sidewalk width near curb ramp crossing on south side of parking area is only 3'-9", need zoning and engineering approval to remain as is. 3) Stabilize all exposed areas per LUC 3.7.2.7. You may request the use of a soil stabilizer in lieu of conventional site soil stabilization requirements, however this will need to be approved by the DSD engineering reviewer. As-built are OK if items listed above are fixed in the field, otherwise change as-builts to reflect what was built. |