Inspection History: POOL/SPA ELECTRIC

Permit Number - T07BU02596

Inspection Description - POOL/SPA ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
06/05/2008 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
04/04/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1. OK POTTING COMPOUND WET NICHE FIXTURE
2. INSTALL WEATHERPROOF COVER @ TIMER SWITCH
3. DO NOT HAVE PROPER WORKING CLEARANCE IN FRONT OF PANEL
4. RECALL WHEN SPA OPERATIONAL FOR COMPLETE FINAL
02/12/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1. OK CUPS FOR HANDRAIL
2. OK EQUAPOTENTIAL BOND GRID
3. RECALL FOR FINAL WHEN READY
01/31/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1. OK ELECTRIC & BONDING @ SPA
2. OK U.G TO EQUIPMENT LOCATION
3. RECALL FOR EQUAPOTENTIAL BOND GRID BEFORE INSTALLING COOL DECK
01/30/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EQUIPMENT BOND GRID TO BE CONNECTED TO ALL 4 SIDES OF SPA NOT JUST 2 -- NEC 680.26 2008
2. ALL PVC DEPTHS TO BE MIN. 18" SEE NEC 680.10
3. DO NOT GUNITE SPA
4. RECALL WHEN READY
01/29/2008 POOL/SPA ELECTRIC Cancelled IVRS - RI canceled