Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T07BU02596
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2008 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
| 04/04/2008 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1. OK POTTING COMPOUND WET NICHE FIXTURE 2. INSTALL WEATHERPROOF COVER @ TIMER SWITCH 3. DO NOT HAVE PROPER WORKING CLEARANCE IN FRONT OF PANEL 4. RECALL WHEN SPA OPERATIONAL FOR COMPLETE FINAL |
|
| 02/12/2008 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1. OK CUPS FOR HANDRAIL 2. OK EQUAPOTENTIAL BOND GRID 3. RECALL FOR FINAL WHEN READY |
|
| 01/31/2008 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1. OK ELECTRIC & BONDING @ SPA 2. OK U.G TO EQUIPMENT LOCATION 3. RECALL FOR EQUAPOTENTIAL BOND GRID BEFORE INSTALLING COOL DECK |
|
| 01/30/2008 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EQUIPMENT BOND GRID TO BE CONNECTED TO ALL 4 SIDES OF SPA NOT JUST 2 -- NEC 680.26 2008 2. ALL PVC DEPTHS TO BE MIN. 18" SEE NEC 680.10 3. DO NOT GUNITE SPA 4. RECALL WHEN READY |
|
| 01/29/2008 | POOL/SPA ELECTRIC | Cancelled | IVRS - RI canceled |