Inspection Status: Approved
Inspection History: GRADING - INTERMEDIATE
Permit Number - T07BU02518
Inspection Description - GRADING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2008 | GRADING - INTERMEDIATE | Approved | ||
| 12/06/2007 | GRADING - INTERMEDIATE | Correction Required | 1) ENSURE STORM WATER PUMPED FROM LOADING RAMP MAKES IT TO THE PARKING LOT. 2) ENSURE STORM WATER IN PARKING AREA DRAINS AWAY FROM BLDG AND FOLLOWS FLOW PATTERNS SHOWN ON THE APPROVED PLAN. - TO INCLUDE FLOW OUT OF CURB OPENINGS SHOWN ON SOUTH SIDE OF LOT. 3) PROVIDE AN ADA COMPLIANT PEDESTRIAN CIRCULATION PATHWAY FROM THE RIGHT-OF-WAY TO THE BLDG. 4) PROVIDE SCUPPERS FOR ALL ROOF DOWN SPOUTS THAT DRAIN ONTO THE ADJACENT SIDE WALK. |