Permit: T07BU02498

Parcel: 136290180


Addresses:

4701 S ALMOND ST

Inspection Status: Approved

Inspection History: POOL/SPA PRE-GUNITE

Date Description Inspector Results Comments
01/07/2008 POOL/SPA PRE-GUNITE Approved IVRS - Inspection :*
01/04/2008 POOL/SPA PRE-GUNITE Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/21/2007 POOL/SPA PRE-GUNITE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE ENGINEERING FOR ALTERNATE RELIEF SYSTEM (MDX DRAIN) AND HAVE APPROPRIATE CONNECTIONS UNCOVERED
2) FILL BLANK SPACES IN ELECTRIC PANEL AND LABEL ALL BREAKERS ASSOCIATED WITH POOL
3) PROVIDE NUMBER BONDING WIRE AROUND POOL OR 4 LEADS TO PERMIT INSTALLATION AT A LATER DATE