Inspection History Details
Inspection Status: Approved
Inspection History: GRADING - INTERMEDIATE
Permit Number - T07BU02487
Inspection Description - GRADING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/22/2010 | GRADING - INTERMEDIATE | Approved | ||
09/16/2010 | GRADING - INTERMEDIATE | Continued | DON WITH LLOYD CONSTRUCTION 471-8421. PROVIDE AN AS-BUILT DRAWING THE FINAL GRADING INSPECTION THAT IS APPROVED BY THE COT AND SHOWS WHAT WAS CONSTRUCTED |
|
04/30/2010 | GRADING - INTERMEDIATE | Continued | NO SIGNIFICANT STORM WATER CONCERNS AT THIS TIME. STORM DRAINAGE SYSTEM HAS BEEN INSTALLED ALONG PERIMETER OF SITE, AWAITING BLDG COMPLETION |
|
02/10/2010 | GRADING - INTERMEDIATE | Continued | CONTRACTOR INSTALLED 6" PERIMETER DRAIN ALONG WEST, SOUTH AND EAST (NE) SIDES PER APPROVED SITE/GRADING PLAN - OK TO BURY. NO STORM WATER CONCERNS AT THIS TIME. CONTRACTOR SHOULD CALL IN FUTURE INSPECTIONS UNDER THE GRADING PERMIT T07BU02487 |
|
01/29/2010 | GRADING - INTERMEDIATE | Continued | NO STORM WATER CONCERNS AT THIS TIME - CONT TO SWEEP TRACKING FROM SITE. LITTLE SITE WORK/ ALL CONSTRUCTION ON STRUCTURE | |
01/14/2010 | GRADING - INTERMEDIATE | Partial Approval | Approved installation of 6" perf pipe along the east, north and west edge of site. Pipe bedded in drain rock and wropped in filter cloth. | |
10/28/2009 | GRADING - INTERMEDIATE | Continued | VERY LITTLE SITE WORK ASSOCIATED W/ PROJECT | |
03/11/2009 | GRADING - INTERMEDIATE | Continued | NO ENG. CHANGES SINCE LAST INSPECTION. SITE WORK IS CONSIDERED MINIMAL OUTSIDE THE STRUCTURE | |
01/14/2009 | GRADING - INTERMEDIATE | Correction Required | NO APPROVED GRADING PLAN SHOWING EROSION PROTECTION METHOD DETAILS USED AND/OR STORM WATER MANAGEMENT TECHNIQUES USED FOR THE PERIMETER WALLS (SHOTCRETE/ GEOTECH MATTING) OF THE PARKING STRUCTURE. CONTRACTOR NEEDS TO PROVIDE THOSE. |