Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T07BU02467
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/19/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* HOOD IS NOT TYPE 1 HOOD HOOD & MUA NOT INTERLOCKED CANNOT CONFIRM TYPE 1 GREASE DUCT E.F ELECTRICAL NOT APPROVED METHODS E.F NOT PROPERLY TERMINATED ON ROOF WALL FLASHING NOT PROPERLY INSTALLED BREAD OVEN NOT APPROVED APPLIANCE |
|
12/18/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE HAVE SOMEONE AVAILABLE WHEN CALLING FOR INSPECTION |