Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T07BU02446

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/03/2007 FIRE - KITCHEN EXH HOOD FINAL Approved
11/29/2007 FIRE - KITCHEN EXH HOOD FINAL Not ready for Inspection
11/26/2007 FIRE - KITCHEN EXH HOOD FINAL Denied REMOVE PIGTAILS INSIDE HEAD CONTROL BOX. EXHAUST FAN SHUT DOWN DURING TEST. ELECT. RECEPT UNDER HOOD DID NOT LOSE POWER DURING TEST. NEED 8" SLASH GUARD ON SYSTEM #3 FRYER. SERVICE "K" EXTINGUISHER.