Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07BU02412

Parcel: 105095510


Addresses:

4701 N STONE AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07BU02412

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/28/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/02/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MC TO BE SECURED WITHIN 12" OF TERMINATIONS
2. PROPER MC CONNECTORS ARE TO BE USED, NOT ROMEX CONNECTOR
3. USE MC STRAPS, NOT 1/2" EMT
4. SECURE EMT WITHIN 36" OF ENCLOSURES
5. GROUND J-BOXES
6. FLEX CONNECTOR ON EMT?
7. SECURE EXIT SIGNS
8. PLANS SHOW 16GA CONDUCTOR FOR 24V CKT
9. WIRING NOT PER PLAN, DOES NOT SHOW TRANSFORMER INSTALLATION, REVISE PLAN AND PROVIDE TRANSFORMERS INSTALL MANUAL.