Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07BU02412
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/28/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/02/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MC TO BE SECURED WITHIN 12" OF TERMINATIONS 2. PROPER MC CONNECTORS ARE TO BE USED, NOT ROMEX CONNECTOR 3. USE MC STRAPS, NOT 1/2" EMT 4. SECURE EMT WITHIN 36" OF ENCLOSURES 5. GROUND J-BOXES 6. FLEX CONNECTOR ON EMT? 7. SECURE EXIT SIGNS 8. PLANS SHOW 16GA CONDUCTOR FOR 24V CKT 9. WIRING NOT PER PLAN, DOES NOT SHOW TRANSFORMER INSTALLATION, REVISE PLAN AND PROVIDE TRANSFORMERS INSTALL MANUAL. |