Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/05/2008 |
FIRE - KITCHEN EXH HOOD FINAL |
|
Approved |
|
| 03/03/2008 |
FIRE - KITCHEN EXH HOOD FINAL |
|
Denied |
SYSTEM NOT TRIPPING WHEN TEST LINK IS CUT |
| 02/22/2008 |
FIRE - KITCHEN EXH HOOD FINAL |
|
Denied |
NEED SPLASH GUARD ON FRYERS. EXHAUST FAN SHUT DOWN DURING TEST. APPLIANCES MUST BE 6" UNDER HOOD. LEAVE BACK SHELVE OFF OF RANGES. ALIGN NOZZLE OVER CHAR BOILER. NEED F.A. INSP. REPORT |