Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
03/05/2008 FIRE - KITCHEN EXH HOOD FINAL Approved
03/03/2008 FIRE - KITCHEN EXH HOOD FINAL Denied SYSTEM NOT TRIPPING WHEN TEST LINK IS CUT
02/22/2008 FIRE - KITCHEN EXH HOOD FINAL Denied NEED SPLASH GUARD ON FRYERS. EXHAUST FAN SHUT DOWN DURING TEST. APPLIANCES MUST BE 6" UNDER HOOD. LEAVE BACK SHELVE OFF OF RANGES. ALIGN NOZZLE OVER CHAR BOILER. NEED F.A. INSP. REPORT