Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T07BU02357
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/29/2008 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
02/26/2008 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE #8 COPPER GREEN INSULATED WIRE TO GROUND LIGHTS 2) COVER CONNECTIONS IN LIGHTS WITH APPROVED POTTING COMPOUND TO PROTECT COPPER WIRE FROM CORROSION 3) BARRIER OK PENDING OTHER FINALS 4) NO SVRS REQUIRED 5) T/P VALVE IS TO BE INSTALLED IN A VERTICAL POSITION |
|
02/14/2008 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOTE: BOTH LIGHT NOT TO EXCEED 12 AMPS 25 PERCENT OF 15 AMP CIRCUIT 2) BOTH POOL LIGHTS REQUIRE AN INSULATED #8 COPPER WIRE FROM WET NICHE FIXTURE TO J-BOX . EXPOSE COPPER CONNECTION INSIDE LIGHT CAN TOO BE ENCAPSULATED WITH APPROVED POTTING COMPOUND TO PROTECT EXPOSED COPPER 3) TIE ALL BONDS TOGETHER RUN BACK TO MOTORS BOTH J-BOXES TO BE BONDED 4) #14 WIRE FOR LIGHT PROTECTED BY 20 AMP BREAKER 5) IF METAL FENCE IS TO BE CLOSER THAN 5' TO THE H20 IN THE POOL NEED A BOND JUMPER FROM BOND GRID RUN IT WILD 5) NOTE: CHECK ALL BOND CONNECTIONS |
|
12/04/2007 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* |