Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07BU02357

Parcel: 141300550

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Permit Number - T07BU02357

Inspection Description - POOL/SPA ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
02/29/2008 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
02/26/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE #8 COPPER GREEN INSULATED WIRE TO GROUND LIGHTS
2) COVER CONNECTIONS IN LIGHTS WITH APPROVED POTTING COMPOUND TO PROTECT COPPER WIRE FROM CORROSION
3) BARRIER OK PENDING OTHER FINALS
4) NO SVRS REQUIRED
5) T/P VALVE IS TO BE INSTALLED IN A VERTICAL POSITION
02/14/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NOTE: BOTH LIGHT NOT TO EXCEED 12 AMPS 25 PERCENT OF 15 AMP CIRCUIT
2) BOTH POOL LIGHTS REQUIRE AN INSULATED #8 COPPER WIRE FROM WET NICHE FIXTURE TO J-BOX . EXPOSE COPPER CONNECTION INSIDE LIGHT CAN TOO BE ENCAPSULATED WITH APPROVED POTTING COMPOUND TO PROTECT EXPOSED COPPER
3) TIE ALL BONDS TOGETHER RUN BACK TO MOTORS BOTH J-BOXES TO BE BONDED
4) #14 WIRE FOR LIGHT PROTECTED BY 20 AMP BREAKER
5) IF METAL FENCE IS TO BE CLOSER THAN 5' TO THE H20 IN THE POOL NEED A BOND JUMPER FROM BOND GRID RUN IT WILD
5) NOTE: CHECK ALL BOND CONNECTIONS
12/04/2007 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*