Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2008 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
| 12/04/2007 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1) BONDING GRID OK |
|
| 11/21/2007 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 4 #8 IN PLACE FOR GRID |
|
| 11/16/2007 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1) CONDUIT LIGHT TO EQUIPMENT AREA OK 2) BONDING OF EQUIPMENT OK 3) PER 2006 IRC, E4104.4, A BONDING GRID 3' BEYOND THE POOL IS REQUIRED 4) AN APPEAL MAY PERMIT THE USE OF A #8 COPPER WIRE SURROUNDING THE POOL AND ATTACHED AT 4 POINTS TO THE POOL GRID |