Permit: T07BU02249

Parcel: 116300160

Inspection Status: Approved

Inspection History: POOL/SPA PRE-GUNITE

Permit Number - T07BU02249

Inspection Description - POOL/SPA PRE-GUNITE

Inspection Status - Approved

Date Description Inspector Results Comments
11/28/2007 POOL/SPA PRE-GUNITE Approved IVRS - Inspection :*
11/23/2007 POOL/SPA PRE-GUNITE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SITE PLAN DOESN'T INDICATE POOL EDGE AT EDGE OF WASH.
2. BECAUSE THE ENTIRE EAST WALL IS FREE STANDING PLEASE HAVE ONLY REBAR SCHEDULE PERTAINING TO THIS POOL IN PACKET, PLEASE HIGHLIGHT PORTION REQUIRED I'M LOOKING AT 6'0" AT 6" O.C #3, ALSO, CALLS FOR 4 NUMBER 3 AT TOP OF NAIL YOU HAVE 3
3. IN NEW IRC 2006 REQ. FOR DECK REBAR GRID CITY IS ALLOWING A #6 CU WIRE ATTACHED TO MAIN REBAR GAUGE 4 SIDES OK SIDES WITH DECK CAN BE BURIED, RUN #6 ON TOP OF EAST WALL FOR CONTINUOUS LOOP.