Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA PRE-GUNITE
Permit Number - T07BU02249
Inspection Description - POOL/SPA PRE-GUNITE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/28/2007 | POOL/SPA PRE-GUNITE | Approved | IVRS - Inspection :* | |
11/23/2007 | POOL/SPA PRE-GUNITE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SITE PLAN DOESN'T INDICATE POOL EDGE AT EDGE OF WASH. 2. BECAUSE THE ENTIRE EAST WALL IS FREE STANDING PLEASE HAVE ONLY REBAR SCHEDULE PERTAINING TO THIS POOL IN PACKET, PLEASE HIGHLIGHT PORTION REQUIRED I'M LOOKING AT 6'0" AT 6" O.C #3, ALSO, CALLS FOR 4 NUMBER 3 AT TOP OF NAIL YOU HAVE 3 3. IN NEW IRC 2006 REQ. FOR DECK REBAR GRID CITY IS ALLOWING A #6 CU WIRE ATTACHED TO MAIN REBAR GAUGE 4 SIDES OK SIDES WITH DECK CAN BE BURIED, RUN #6 ON TOP OF EAST WALL FOR CONTINUOUS LOOP. |