Permit: T07BU02179

Parcel: 12911052A


Addresses:

1050 E 22ND ST


Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Permit Number - T07BU02179

Inspection Description - MECHANICAL - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
10/25/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE ENGINEERED DRAWINGS TO INSTALL TYPE 1 HOOD, GREASE DUCT, EXHAUST FAN, ETC.
10/24/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE COVER ON EF
2. USE APPROVED SEAL-TITE CONNECTORS ON M.U.A POWER
3. MUA & E.F HOOD OVERFUSED NOT PROPERLY WIRED
4. WALL BEHIND HOOD NOT PROPERLY SEALED
5. PROVIDE AIR BALANCE REPORT FOR HOOD
6. FIRE SUPPRESSION PIPING NOT PROPERLY ANCHORED