Permit: T07BU02080

Parcel: 11628001L

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Permit Number - T07BU02080

Inspection Description - POOL/SPA ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
05/06/2008 POOL/SPA ELECTRIC Approved
03/10/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK PVC U.G FROM EAST GATE
AROUND OUTSIDE NORTHSIDE OF LAZY RIVER
OK NORTH EAST OF LAZY RIVER
02/19/2008 POOL/SPA ELECTRIC Not ready for Inspection IVRS - Inspection :*
02/13/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK SEALANT FOR BONDING OF WET NICHE LIGHT FIXTURE
02/05/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK REMAINDER OF BONDING LAZY RIVER & SLIDE AREA
01/31/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK BONDING OUTSIDE OF SECTIONS 3 & 4 BRIDGE AREA
01/28/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK SECTION #5 & LIGHTING CONDUITS EXCEPT PERIMETER GROUND
01/18/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK ISLAND SIDE OF SECTIONS #3 & #4 FOR PERIMETER GROUNDING
01/16/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK HOMERUN CONDUITS TO EQUIP. BLD NORTH
OF SECTION #6, SOUTH SECTION 6 & PART OF 5
01/15/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK SECTION #4 LTG. CONDUITS SOUTH SIDE
01/14/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK EQUIP. ROOM BELOW SLAB
01/11/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
CODE ALLOWS 360 DEG. MAX IN BENDS BETWEEN PULL OR TERMINATION POINTS. PER 352.26 NEC, PVC
01/10/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
- N.W AREA OF ISLAND FOR PERIMETER GROUNDING
- OK CONDUITS TO LTG. J.BOX BY SLIDE ENTRY AREA AND HOME RUN TO ELECTRIC ROOM
01/07/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK BONDING TO ANCHORS & PERIMETER GROUNDING FOR SECTIONS #1, #2, #3
01/04/2008 POOL/SPA ELECTRIC Not ready for Inspection IVRS - Inspection :*
12/31/2007 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK SECTION #6 AND PARTIAL HOMERUNS ON NORTH SIDE OF LAZY RIVER EXCEPT AT CONTROL BLD. SECTIONS #1, #2, #3
12/26/2007 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) OK GUNITE SECTION #4
12/20/2007 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
- OK SECTIONS #2 & #3 REBAR GROUNDING, LIGHTS, AND #8 GROUND TAILS FOR PERIMETER GROUND
- RECEIVED SUBMITTAL CUT SHEETS FOR LIGHT FIXTURES
OK GUNITE SECTIONS #2 & #3 SUBJECT TO OTHER INSPECTORS APPROVAL
12/17/2007 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
- OK PARTIAL GUNITE & GROUNDING AT SECTION
- #1, CONTR. TO HAVE CUT SHEET ON LIGHT FIXTURES LIGHTING CONDUITS STUB OUT ONLY
- INSPECTOR TO CONTACT PATIO POOL, CONTACT PERSON IS STEVE (940-3711) CONCERNING GROUND GRID OUTSIDE OF POOL, PER 680.26 NEC
DO NOT COOL DECK PRIOR TO INSPECTORS APPROVAL
POOL CONTR. WILL STUB OUT A #8 GROUND AT EACH SECTION FOR PERIMETER GROUNDING.