Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK RECEIVED LETTER FROM MONROD ENGINEERING CONCERNING FEEDER FROM MAIN BLD. DIST. PANEL |
|
| 04/15/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* - OK WORK DONE CHUCKS ELECTRIC WAITING FOR ENGINEER REPORT ON FEEDERS TO POOL BLD PUMP HOUSE PER MARRIOT REPRESENTATIVE THESE FEEDERS TO PUMP HOUSE WERE INSTALLED BY OTHERS |
|
| 04/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - GROUNDING ELECTRODE FOR BLD. NEEDS TO BE TIED INTO MAIN POWER GROUND BAR & SIZED PER 250.66 NEC PER 250.32 - COULD NOT VERIFY PANEL SCHEDULES FOR PANELS INSIDE CONTROL BLD. - PARAPET LTG. TO BE INSTALLED IN FUTURE PER LETTER FILED |
|
| 03/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* BOLLARD LIGHTS WORKING |
|
| 03/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FOR TCO LV LIGHT FIXTURE IN WALL NOT IN YET |