Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T07BU02046
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/06/2008 | FIRE SPKLR - FINAL | Approved | ||
02/01/2008 | FIRE SPKLR - FINAL | Denied | MAIN IS BOWED. HEAD OBSTRUCTED BY METAL FRAME. HEAD STUCK IN WALL IN LAUNDRY ROOM. MANAGERS OFFICE HEAD TOO CLOSE TO THE WALL. NEED TO ISPECT LOBBY AREA WHEN CONSTRUCTION IS DONE. |