| 11/21/2007 | POOL/SPA PRE-GUNITE | Not Applicable | IVRS - Inspection :* | |
| 11/19/2007 | POOL/SPA PRE-GUNITE | Partial Approval | IVRS - Inspection :* 1) REBAR OK-SEE ELECTRIC 2) EQUIPMENT NOT SET 3) PAINT PVC PIPE 4) BOND WIRE AND CONDUIT TO LIGHT OK 5) CONDUIT FOR EQUIPMENT NOT RUN 6) COMPLY WITH 2006 IRC; E4104.4 (BONDING GRID) WITH PERMISSION OF BLDG OFFICIAL, A #8 BARE COPPER CAN SURROUND THE POOL AND BE CONNECTED TO THE REBAR CAGE AT 4 LOCATIONS |