Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/13/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE PROPER BANDING ON FIRE WRAP 2. REMOVE ACCESS FOR INSPECTION (DOOR) 3. PROVIDE GREASE TROUGH ON ROOF 4. PROVIDE CHAIN ON ROOF TO SUPPORT EXHAUST FAN 5. PROPERLY SEAL ROOF CURB ON EXHAUST FAN 6. REMOVE BOLTS PENETRATING HOOD |
|
| 03/24/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - 1ST LAYER OF GREASE DUCT WRAP OK - PROVIDE PROPER ACCESS DOOR PRIOR TO SECOND LAYER OF WRAP - PROVIDE INSTALLATION INSTRUCTIONS FOR ACCESS DOOR AND INSULATION PRIOR TO NEXT INSPECTION - MAINTAIN 3" OVERLAP AT SECOND LAYER OF WRAP |
|
| 03/17/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* LIGHT TEST ON GREASE DUCT OK OK FOR 1ST LAYER WRAP |
|
| 03/13/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
| 03/13/2008 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* REFEE WILL APPLY TO NEXT INSPECTION |
|
| 03/07/2008 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/05/2008 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/25/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FOR SECOND LAYER OF WRAP |