Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/22/2007 | FIRE SPKLR - FINAL | Approved | ||
| 10/15/2007 | FIRE SPKLR - FINAL | Denied | 1. IN URGENT CARE STORAGE ROOM BY EMPLOYEE ROOM, SPRINKLER HEAD IS 8 FEET OFF WALL ONLY 7' 6" ALLOWED. 2. (URGENT CARE) BY NURES STATION SPRINKLER HEADS 11' 7" OFF WALL ONLY 7' 6" ALLOWED. NEED TO CORRECT COVERAGE IN BOTH AREAS. |