Permit: T07BU01740

Parcel: 115180050


Addresses:

1601 N ORACLE RD

Inspection Status: Denied

Inspection History: POOL/SPA ELECTRIC

Date Description Inspector Results Comments
04/16/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE LISTED POOL JUNCTION BOXES FOR LIGHTS
2. TIGHTEN LOOSE FITTINGS & SUPPORT CONDUITS
3. SEAL ENTRANCES ABOVE TOP OF PANEL
4. A MAIN DISCONNECTING MEANS IS NEEDED FOR POOL PANEL P1
5. INSTALL LISTED GROUND BAR & KIT
6. MAINTAIN WORKING CLEARANCES AT DISCONNECTS
7. LABEL DISCONNECTS
8. WHERE IS POOL EQUIPMENT BONDS
9. USE LISTED ENCLOSURES & FITTINGS FOR WET LOCATON
1O. SPLICES TO BE FOR WET LOCATION
03/28/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
03/26/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
NO WORK PROGRESS
01/24/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAIN BACKFED BREAKER TO HAVE MANUFACTURES HOLD DOWN
2. FINISH #8, 10 AND 11 - WHAT IS A RELAY? UNCOVER CONDUIT TO INSPECT
3. NEED ELECTRICIAN PRESENT TO LOOK AT MAIN SERVICE
01/15/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. JUNCTION BOX - CLEAN SURFACE UNDER LUG AND USE APPROVED MEANS OF ATTACHMENT - NOT DRYWALL/WOOD SCREW
2. A GROUNDING ELECTRODE SYSTEM IS NEEDED
3. SEPARATE GROUNDS AND NEUTRALS
4. USE COLORS FOR CONDUCTORS AS PER
CITY AMENDMENT 210.5
5. DERATE CONDUCTORS PER 310.15
6. SUPPORT PVC CONDUIT BELOW PANEL
7. CONDUCTOR MARKING TAPE TO ENCIRCLE CONDUCTOR
8. PANEL NEEDS A MAIN DISCONNECTING MEANS
9. LABEL OUTSIDE COVER OF PANEL
10. CIRCUIT DIRECTORY TO BE AS PER 408.4 -
NO ABBREVIATIONS
11. CONDUIT TO BE AS PER 300.5 - 18" DEPTH
12. GROUND SWITCHBOX JUNCTION BOX
12/05/2007 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK DECK TO POUR
OK FOR FIBER OPTICS IN CONDUIT PER DISCUSSIONS
11/28/2007 POOL/SPA ELECTRIC Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
CODES APPLICABLE 770.12(A), 352.26

1. SPLIT BOLT LISTED FOR 2 CONDUCTORS ONLY
2. BOND WIRE TO BE 18" - 24" FROM EDGE
3. WHERE ARE RAIL CUPS?

DO NOT COVER OR POUR
11/23/2007 POOL/SPA ELECTRIC Denied IVRS - Inspection :
There is no access to the site.| 920*
GATE LOCKED NO ACCESS - NO ANSWER FROM NICK
POURED WITHOUT INSPECTIONS APPROVED PLEASE UNCOVER
11/09/2007 POOL/SPA ELECTRIC Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL FORMING SHELL
2. NO MORE THAN 360 DEG. IN A CONDUIT RUN

* WILL NEED TO SEE DECK BOND GRID

DO NOT POUR