Permit: T07BU01709

Parcel: 11612067B


Addresses:

1202 W NIAGARA ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/21/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- HOOD APPEARS TO BE TYPE 1
- HOWEVER, THE EXHAUST FAN & RELATED DUCT
ARE NOT TYPE 1
- CANNOT CONFIRM GREASE DUCT IS IN A RATED SHAFT OR FIRE WRAPPED.
08/16/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE SCHEDULE AN INSPECTION WHEN SOMEONE CAN BE HERE AT 8:00 AM