Permit: T07BU01427

Parcel: 138111720


Addresses:

6107 S 6TH AV

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/28/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- DO NOT SPLICE ELEC. WIRES OUTSIDE OF THE JUNCTION BOX IN EXHAUST FAN.
- PROVIDE A SWITCH IN FAN.
- PROVIDE AN APPROVED ENGINEERED SET OF PLANS.
- PROVIDE A MAKE UP AIR IN KITCHEN & INTERLOCK WITH HOOD.
07/24/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
THE DUCT & FAN ON ROOF ARE NOT TYPE I
THERE IS NO MAKE UP AIR
THE HOOD APPEARS TO BE TYPE I APPROVED BY IMC.
THERE ARE SOME HOLES THAT NEED TO BE SEALED
CANNOT CONFIRM GREASE DUCT IS IN A RATED SHAFT
07/09/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
SCHEDULE AN INSPECTION WHEN SOMEONE WILL BE HERE