Permit: T07BU01389

Parcel: 140420150


Addresses:

2660 E MEDINA RD

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Date Description Inspector Results Comments
12/06/2007 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
11/26/2007 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1. USE APPROVED STRAPS TO SUPPORT #8 BARE IN EQUIP. ROOM - CONTR. NOT ON SITE 9:30 AM

RETURN PM INSP. PER CONTR. REQUEST THIS IS AN UNSCHEDULED INSP. $150.00 FEE PAID CK#3342

2. GROUND LUG FOR HOYER LIFT NOT RATED FOR DIRECT BURIAL OR CONCRETE ENCASEMENT
3. ALL CIRCUIT BREAKERS IN EQUIP. PANEL TO BE OF SAME MANUF. AS PANEL. SEE NOTES IN PANEL COVER.
11/16/2007 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO INSPECTIONS FOR GROUNDING CONNECTIONS FOR METALLIC POOL EQUIP. SUCH AS LADDERS, ESCUTIONS OR GROUND CONDUCTORS FOR ENTIRE SYSTEM FROM POOL/SPA TO PUMP EQUIP.
REMOVE COOL DECKING AT THESE POINTS, MUST COMPLY WITH 680.26 NEC FOR GROUNDING AND 250.8 NEC
2. HAVE PLANS/PERMIT ON SITE
3. SEE NOTES PREVIOUS INSP. ON 9/12/07
4. BONDING IN POOL EQUIP. ROOM TO BE DONE IN WORKMANSHIP LIKE MANNER - USE STRAPS TO SUPPORT #8 TO CONCRETE FLOOR.
09/12/2007 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
- OK GROUNDING OF REBAR, CALL FOR INSPECTION BEFORE COOL DECK, MUST INSPECT CONNECTIONS TO ESCUTIONS, LADDERS, ETC. PRIOR TO COVERING
- OK UNDERGROUND PVC FOR POWER, LTG. OR GUNITE