Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T07BU01386
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/30/2008 | FIRE SPKLR - FINAL | Approved | ||
08/14/2007 | FIRE SPKLR - FINAL | Not ready for Inspection | ||
07/20/2007 | FIRE SPKLR - FINAL | Denied | Need heads under garage doors southwest corner x 2. Add heads in north end storage room. Need as bults. Need monitor system for water flow. Need to monitor or pad locks all PIV's and Butterfly valves. Need head Box with extra sprinkler heads. Need to sign all valves on riser and Hyd Cal Plates. Label Risers 1,2,3 or A, B, C, etc. |