Inspection History: FIRE SPKLR - FINAL

Permit Number - T07BU01386

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/30/2008 FIRE SPKLR - FINAL Approved
08/14/2007 FIRE SPKLR - FINAL Not ready for Inspection
07/20/2007 FIRE SPKLR - FINAL Denied Need heads under garage doors southwest corner x 2.
Add heads in north end storage room. Need as bults.
Need monitor system for water flow.
Need to monitor or pad locks all PIV's and Butterfly valves.
Need head Box with extra sprinkler heads.
Need to sign all valves on riser and Hyd Cal Plates.
Label Risers 1,2,3 or A, B, C, etc.