Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA PLUMBING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2008 | POOL/SPA PLUMBING | Approved | IVRS - Inspection :* | |
| 03/05/2008 | POOL/SPA PLUMBING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLY WITH PREVIOUS NOTES 3 & 4 2) SOLAR TO BE REMOVED BY OWNER |
|
| 02/06/2008 | POOL/SPA PLUMBING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL CIRCUITS SUB PANEL 2) LEAK AT PUMP 3) COMPLY WITH PREVIOUS NOTES 2, 5, 9 & 10 4) ALSO WEST BARRIER FOOTHOLDS ON OPPOSITE SIDE OF POOL FENCE |
|
| 01/03/2008 | POOL/SPA PLUMBING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FENCE AT EAST SIDE YARD, TO BE 5'-0" HIGH NON CLIMABLE, SECURED TO WALLS AND GROUND 2) NOTHING ON PLAN FOR SOLAR, LEAKING PIPES AT TIMER AND AT PUMP 3) UNABLE TO READ UL LABEL ON OLD PUMP 4) OVERHEAD SERVICE WIRES TO CLOSE TO POOL 5) UNABLE TO LOCATE LIGHT J-BOX-GFCI PROTECTION 6) NO MAIN BOND WIRE FROM POOL TO MOTOR 7) NO DISCONNECTING MEANS FOR POOL MOTOR, YOU NEED AN LICENSED ELECTRICIAN TO GO THRU ALL WIRING 8) SERVICE ENTRANCE EQUIPMENT IS IN A HAZARDOUS STATE 9) UNABLE TO DETERMINE WERE POWER FOR POOL COMES FROM 10) GLAZE TO POOL NOT SELF CLOSING 1 LATCHING 11) STOPPED INSPECTION |