Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/04/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* OK TO INSTALL GREASE DUCTS ALREADY FIRE WRAPPED |
|
| 07/12/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE HOOD MEETS TYPE 1 REQUIREMENTS HOWEVER, THE GREASE DUCTS ARE NOT TYPE 1 DUCTS NEED TO BE 16ga. WELDED SEAMS WITH FIRE WRAP OR 1 HR CHASE CANNOT CONFIRM EXHAUST FANS TO BE TYPE 1 A TYPE 1 FAN TYPICALLY DOES NOT DISCHARGE THE AIR ONTO THE ROOF. THERE ARE UTILITY FANS USED FOR BATHROOM EXHAUST, ETC. EXHAUST FANS MUST BE INTERLOCKED WITH MAKE UP AIR UNIT |