Permit: T07BU01319

Parcel: 115080230


Addresses:

333 W DRACHMAN ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/12/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/04/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
OK TO INSTALL GREASE DUCTS ALREADY FIRE WRAPPED
07/12/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
THE HOOD MEETS TYPE 1 REQUIREMENTS
HOWEVER, THE GREASE DUCTS ARE NOT TYPE 1
DUCTS NEED TO BE 16ga. WELDED SEAMS WITH FIRE WRAP OR 1 HR CHASE
CANNOT CONFIRM EXHAUST FANS TO BE TYPE 1
A TYPE 1 FAN TYPICALLY DOES NOT DISCHARGE THE AIR ONTO THE ROOF. THERE ARE UTILITY FANS USED FOR BATHROOM EXHAUST, ETC.
EXHAUST FANS MUST BE INTERLOCKED WITH MAKE UP AIR UNIT