Permit: T07BU01307

Parcel: 13414018N


Addresses:

7501 E 22ND ST


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T07BU01307

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/10/2008 FIRE SPKLR - FINAL Approved
01/04/2008 FIRE SPKLR - FINAL Not ready for Inspection Correct sprinkler coverage in the following areas:
1.Northeast corner show room floor by door head 8' 6" from wall
2.Office storage room heads 9' off wall (x2) only 7' 6" allowed
3.Soffit above sale counter heads over 8' need to install heads in soffit.
4.Sales floor (southeast) at the start of the ceiling change from 14' to 8', heads 8' from change need to cover dead spot area.