Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T07BU01307
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2008 | FIRE SPKLR - FINAL | Approved | ||
| 01/04/2008 | FIRE SPKLR - FINAL | Not ready for Inspection | Correct sprinkler coverage in the following areas: 1.Northeast corner show room floor by door head 8' 6" from wall 2.Office storage room heads 9' off wall (x2) only 7' 6" allowed 3.Soffit above sale counter heads over 8' need to install heads in soffit. 4.Sales floor (southeast) at the start of the ceiling change from 14' to 8', heads 8' from change need to cover dead spot area. |