Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA PRE-GUNITE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2007 | POOL/SPA PRE-GUNITE | Approved | IVRS - Inspection :* | |
| 06/08/2007 | POOL/SPA PRE-GUNITE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ON PLOT PLAN, DRAWING SHOWS A DIMENSION OF 4'-0" FROM WALL TO EDGE OF POOL N.W. CORNER. THE DIMENSION IS ONLY 27". ON OTHER SIDE OF POOL IS A MAIN WASH. IS MORE REINFORCING STEEL NEEDED ? NEED LETTER FROM ENGINEER STATING OK AS IS OR NEED MORE REBAR |