Permit: T07BU01032

Parcel: 116267620

Inspection Status: Approved

Inspection History: STEM WALL/RETAINING WALL

Date Description Inspector Results Comments
06/12/2007 STEM WALL/RETAINING WALL Approved IVRS - Inspection :*
06/08/2007 STEM WALL/RETAINING WALL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RETAINING WALL ON SITE DOES NOT MATCH WITH APPROVED PLANS REGARDING 3' HEIGHT, AND COMPLETE MEASURE 30' PROVIDE PROPER HEIGHT OR NEW REVISION ON APPROVED PLANS.
06/06/2007 STEM WALL/RETAINING WALL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE HORIZONTAL LAP SPLICE OR OVERLAP ON REINFORCING 2 #4 CONT. AT LEAST 20" MIN. OVERLAP
2 #4 REBAR = 1/2"
IN ACCORDANCE WITH 1806 IBC AND 1805.5.2.2
ACI 530.1/ASCE 6/TMS 401