Permit: T07BU00976

Parcel: 12710084B


Addresses:

6210 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/23/2007 MECHANICAL - FINAL Approved OK TO INSTALL FIRE SUPPRESSION SYSTEM
06/04/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
TYPE 1 HOOD & GREASE DUCT ARE OK
HOWEVER, THE PADDLE TYPE BLOWER WHEEL HAS BEEN REPLACED WITH A SQUIRREL CAGE (NOT APPROVED FOR
TYPE 1) THE CLEANOUT IS OPEN & NOT TO CODE -- NEEDS 16 GA. STEEL ACCESS DOOR WITH WING NUTS. THE BELT & PULLEYS MUST HAVE A PROTECTIVE COVER.