Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2007 | MECHANICAL - FINAL | Approved | OK TO INSTALL FIRE SUPPRESSION SYSTEM | |
| 06/04/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* TYPE 1 HOOD & GREASE DUCT ARE OK HOWEVER, THE PADDLE TYPE BLOWER WHEEL HAS BEEN REPLACED WITH A SQUIRREL CAGE (NOT APPROVED FOR TYPE 1) THE CLEANOUT IS OPEN & NOT TO CODE -- NEEDS 16 GA. STEEL ACCESS DOOR WITH WING NUTS. THE BELT & PULLEYS MUST HAVE A PROTECTIVE COVER. |