Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2007 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
| 05/04/2007 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 1.) HEADS TO FAR ON WEST BEDROOMS 10' SET FOR 16X16 2.) IN MECH ROOM NOT SHOWING RIGHT SPRINKLER COVERAGE ON PLANS AND PLANS DO NOT REFLECT WHAT IS BUILT. 3.) UNDERGROUND NEEDS TO BE BURIED 30 INCHED IN GROUND NOT 18 INCHES. |