Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07BU00851
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
08/07/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE SCHEDULE AN INSPECTION WHEN SOMEONE CAN BE HERE IN AM 8:00 |
|
06/27/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - WELD 16 GA STEEL PLATES OVER 2 HOLES INSIDE OF GREASE DUCT. - COVER THE GREASE DUCT WITH APPROVED FIRE WRAP. - CLEAN ALL GREASE FROM ROOF AROUND FAN & INSTALL A GREASE CUP ON EXHAUST FAN. |