Inspection History: FIRE SPKLR - FINAL
Permit Number - T07BU00824
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2007 | FIRE SPKLR - FINAL | Not ready for Inspection | NEED AS BUILTS, PLANS DO NOT REFLECT WHAT IS ON SITE | |
08/28/2007 | FIRE SPKLR - FINAL | Denied | 1.) By safe sprinkler head is 8' 1" off wall only 7' 6" allowed 2.) By south east exit plans do not reflect what is on site need as builts 3.) By southeast end of storage room sprinkler heads 8' plus from wall needs to be 7' 6". 4.) Replace painted head by A/C room northeast side (front). 5.) Remove tape off all heads in back storage room West Side by electrical room. |