Permit: T07BU00824


Addresses:

3356 S 6TH AV


Inspection Status: Not ready for Inspection

Inspection History: FIRE SPKLR - FINAL

Permit Number - T07BU00824

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
09/05/2007 FIRE SPKLR - FINAL Not ready for Inspection NEED AS BUILTS, PLANS DO NOT REFLECT WHAT IS ON SITE
08/28/2007 FIRE SPKLR - FINAL Denied 1.) By safe sprinkler head is 8' 1" off wall only 7' 6" allowed
2.) By south east exit plans do not reflect what is on site need as builts
3.) By southeast end of storage room sprinkler heads 8' plus from wall needs to be 7' 6".
4.) Replace painted head by A/C room northeast side (front).
5.) Remove tape off all heads in back storage room West Side by electrical room.