Permit: T07BU00751

Parcel: 141302550

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Permit Number - T07BU00751

Inspection Description - POOL/SPA ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
07/16/2007 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
07/13/2007 POOL/SPA ELECTRIC Not ready for Inspection IVRS - Inspection :*
COMPLETE ITEMS FROM INSPECTION ON 7/12/07
07/12/2007 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT USE SHEETMETAL SCREWS FOR GROUND CONNECTIONS NEED TO ALSO USE STAINLESS SCREWS
2. REMOVE PAINT AT GROUND CONNECTIONS ON FENCES
3. APPEARS ONE OF THE LUGS IS ALSO BROKEN
07/06/2007 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
METAL FENCE WITHIN 5' OF POOL NEEDS TO BE CONNECTED TO BONDING GRID WITH SOLID #8
05/30/2007 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK UNDERGROUND ONLY
05/25/2007 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLY WITH INSPECTION REQUEST ON 5/22/07
2. HAVE SOMEONE MEET ME ON JOB SITE WITH FISH TAPE
3. TO AVOID REFEE PLEASE COMPLY
05/22/2007 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE PVC CONDUIT CAN BE FISH TAPPED
HAVE SOMEONE MEET INSPECTOR ON JOB
05/15/2007 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PVC CONDUIT RUNS BACKFILLED
2. POOL GUNITED
3. CANNOT SEE PVC CONDUIT RUNS
04/27/2007 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SFR TO GO TO RESIDENTIAL INSPECTORS
2. MORE THAN 360 DEG. OF BENDS IN CONDUIT RUNS