Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T07BU00751
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2007 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
07/13/2007 | POOL/SPA ELECTRIC | Not ready for Inspection | IVRS - Inspection :* COMPLETE ITEMS FROM INSPECTION ON 7/12/07 |
|
07/12/2007 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT USE SHEETMETAL SCREWS FOR GROUND CONNECTIONS NEED TO ALSO USE STAINLESS SCREWS 2. REMOVE PAINT AT GROUND CONNECTIONS ON FENCES 3. APPEARS ONE OF THE LUGS IS ALSO BROKEN |
|
07/06/2007 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* METAL FENCE WITHIN 5' OF POOL NEEDS TO BE CONNECTED TO BONDING GRID WITH SOLID #8 |
|
05/30/2007 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* OK UNDERGROUND ONLY |
|
05/25/2007 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLY WITH INSPECTION REQUEST ON 5/22/07 2. HAVE SOMEONE MEET ME ON JOB SITE WITH FISH TAPE 3. TO AVOID REFEE PLEASE COMPLY |
|
05/22/2007 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE PVC CONDUIT CAN BE FISH TAPPED HAVE SOMEONE MEET INSPECTOR ON JOB |
|
05/15/2007 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PVC CONDUIT RUNS BACKFILLED 2. POOL GUNITED 3. CANNOT SEE PVC CONDUIT RUNS |
|
04/27/2007 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SFR TO GO TO RESIDENTIAL INSPECTORS 2. MORE THAN 360 DEG. OF BENDS IN CONDUIT RUNS |