Permit: T07BU00553

Parcel: 13507444E


Addresses:

1551 S EASTSIDE LP


Inspection Status: Continued

Inspection History: GRADING - INTERMEDIATE

Permit Number - T07BU00553

Inspection Description - GRADING - INTERMEDIATE

Inspection Status - Continued

Date Description Inspector Results Comments
05/01/2009 GRADING - INTERMEDIATE Continued FRM T06CM04950
ONE RAMP AT 12% ONE RAMP AT 10% -ADDRESS H/C RAMP LOCATIONS
CP-BIKE RACK NEEDS TO BE INSTALLED 2 CLASS II
CP-GATES ON TRASH ENCLOSURE
-H/C SPACES ARE IN COMPLIANCE
TO BE ADDRESSED WITH GRADING PERMIT T07BU00553
-ADDRESS STOCKPILE IN PHASE 2 PORTION
-STABILIZE PHASE 2 DISTURBED AREA
04/13/2009 GRADING - INTERMEDIATE Continued SCH APPT FOR 15TH
12/17/2008 GRADING - INTERMEDIATE Continued NO ASPHALT FOR LEASE SIGN UP
09/23/2008 GRADING - INTERMEDIATE Continued NO ASPHALT
FORMS UP FOR DRIVEWAY/CURB RETURNS
08/14/2007 GRADING - INTERMEDIATE Continued EMAILED LOREN:
We met and discussed what needs to be done to get an approvable grading plan. They were going to get a new submittal into us this week.
Loren

>>> Nichole Kalahar Zormeier 08/14/2007 7:37 AM >>>
Loren,

I need to know if this plan has been brought back in to you for review. The grading permit is still showing PLAN RFC. Is that the case?

If you don't have the plans in your que he will get a stop work for the site today.

Please call me.

Nichole 240-0153

TALKED TO PAUL AMANTI AND TO BT GROUP (ARCHITECT 419-3025) PLAN TO BE IN TO LOREN BY 8/17
07/05/2007 GRADING - INTERMEDIATE Continued MET WITH LOREN REGARDING THIS PROJECT
NO CHANGES HAVE BEEN SUBMITTED AND HE HAS NOT BEEN CONTACTED BY ARCHITECT/ENGINEER
GRADING PLAN IS STILL NOT APPROVED
06/20/2007 GRADING - INTERMEDIATE Correction Required PLANS SUBMITTED 3/12 FOR GRADING
6/4 PLANS RFC
June 4, 2007
T07BU00553

Grading Plan Comments:

Provide details for the spillways to the concrete drainage channel. Show the interface between the pavement edge and the spillway. Provide cross sections to show the depth of the spillways and the connections to the channel.
Provide a note indicating that all grading will be in conformance with City of Tucson Development Standard 11-01.
Provide a detail for the solid waste enclosure indicating 10 feet of clear space from side to side and from front to back.
Provide the site address on the grading plan as well as a brief legal description.
Provide specifications for the asphalt paving and subgrade.
Provide cut and fill quantities on the grading plan.
On the grading plan, indicate the treatment that will be used for the phase 2 building areas. Will the areas remain undisturbed or will they be graded and stabilized? If they are to be graded, provide pad grade information on the grading plan.
Provide representative cross sections across property lines to show acceptance of off-site flow and grade continuity. Show contours for the areas within 25 feet of the project boundary.
Clearly indicate the grading limits on the grading plan.

The SWPPP plan is accepted for this project.
When the permit application is re-submitted for approval, include three copies of the revised grading plan and three copies of the SWPPP. Include a detailed response letter indicating how each comment has been addressed.

If you have any questions or want to set up a meeting to discuss this grading permit application, I can be reached at 520.837.4927 or at loren.makus@tucsonaz.gov
6/8 PLANS OUT TO CUSTOMER