Permit: T07BU00393

Parcel: 141317220


Addresses:

9080 S OLD OAK CT


Inspection Status: Denied

Inspection History: POOL/SPA PLUMBING

Permit Number - T07BU00393

Inspection Description - POOL/SPA PLUMBING

Inspection Status - Denied

Date Description Inspector Results Comments
06/01/2007 POOL/SPA PLUMBING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POOL GATE STAYS OPEN, NOT SELF CVLOSING, ADJUST HINGE
2) 50 AMP BREAKER IN SERVICE PANEL #8 CU. WIRE FOR EQUIPMENT PANEL
3) 60 AMP BREAKER IN SUB-PANEL FOR HTR ALONE, WITH #14 WIRE BEING PROTECTED
4) LABEL FOR HTR IS BETWEEN HOUSE AND UNIT NEED TO BE ABLE TO READ LABEL FOR CIRCUIT AMPACITY AND OVERCURRENT SIZE
5) SVRS #022936 & #012565
05/30/2007 POOL/SPA PLUMBING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OK TO COVER PIPING AT POOL AREA
2) LOCATE U.L. LABEL FOR CIRCUIT SIZE AND OVER CURRENT PROTECTION, HEATER
3) TWO SVRS UNITS REQUIRED 1 FOR EACH PUMP
4) BOND POOL METAL FENCE
03/26/2007 POOL/SPA PLUMBING Partial Approval IVRS - Inspection :*
1) NOT CONNECTED TO PUMP EQUIPMENT
2) OK TO GUNITE
3) NOT COMPLETE AT THIS TIME
03/23/2007 POOL/SPA PLUMBING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 5 POUNDS OF H20 PRESSURE ON LINES, POOL AREA IS WET
2) ON DETAIL PAGE I COULDN'T FIND A DETAIL, SHOWING LEVEL OF GRADE 3' BELOW TOP OF POOL
3) YOUR PAPERWORK INDICATES A 5'-0" DEEP POOL-IS THAT CORRECT ?
4) PLEASE HIGHLIGHT REBAR SCHEDULE FOR THE RIGHT COLUMN FOR REBAR SPACING