Permit: T07BU00117

Parcel: 116182910


Addresses:

55 N MELROSE AV

Inspection Status: Approved

Inspection History: POOL/SPA FINAL/BARRIER

Date Description Inspector Results Comments
05/30/2007 POOL/SPA FINAL/BARRIER Approved IVRS - Inspection :*
1) SVRS #021163
05/01/2007 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL VACUUM BREAKER HOSE BIB AT AUTO FILL SOURCE
2) ENCLOSURE TO BE MINIMUM 5' HIGH MEASURED FROM OUTSIDE
3) ENCLOSURE FENCE TO BE MINIMUM 20" FROM POOL H20'S EDGE
4) BOND METAL FENCING WITHIN 5' OF POOL EDGE
5) COMPLETE ELECTRIC TO ? CONDUIT AT DETACHED SHED
6) APPEARS SHED SUB PANEL COULD DRAW MORE THAN 40 AMPS. HAVE SHED ELECTRIC CALCULATION TO DETERMINE SIZE OF NEW BREAKER AT SUB-PANEL AND WIRE SIZE
7) INSTALL SVRS-WHAT IS ELECTRIC STUB FOR (STICKING OUT OF KOOL DECK ? )
8) STOPPED INSPECTION