Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T07BU00077
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2007 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
01/25/2007 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1) Electric power under hood system shall shut down when fire extingusher system actvatives. 2) System shall be tied in the fire alarm system. Fire alarm failed to actvative when testing. |
|
01/24/2007 | FIRE - KITCHEN EXH HOOD FINAL | Denied | NO ONE THERE TO DO TEST |