Permit: T07BU00077

Parcel: 124040010


Addresses:

1448 E 1ST ST


Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T07BU00077

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/01/2007 FIRE - KITCHEN EXH HOOD FINAL Approved
01/25/2007 FIRE - KITCHEN EXH HOOD FINAL Denied 1) Electric power under hood system shall shut down when fire extingusher system actvatives.

2) System shall be tied in the fire alarm system. Fire alarm failed to actvative when testing.
01/24/2007 FIRE - KITCHEN EXH HOOD FINAL Denied NO ONE THERE TO DO TEST