Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2007 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
| 01/25/2007 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1) Electric power under hood system shall shut down when fire extingusher system actvatives. 2) System shall be tied in the fire alarm system. Fire alarm failed to actvative when testing. |
|
| 01/24/2007 | FIRE - KITCHEN EXH HOOD FINAL | Denied | NO ONE THERE TO DO TEST |