Case: T06VL00358

Parcel: 11619131A


Addresses:

707 W CONGRESS ST


Inspection Status: Correction Required

Inspection History: INITIAL CODE VIOLATION

Case Number - T06VL00358

Inspection Description - INITIAL CODE VIOLATION

Inspection Status - Correction Required

Date Description Inspector Results Comments
03/08/2006 INITIAL CODE VIOLATION Correction Required 1. SERVICE GARAGE IS IN VIOLATION OF 16-12 B3
ie. IMPROPER REPAIR OF ROOF TRUSS.
2. BREEZEWAY NEXT TO SERVICE GARAGE AND CAR PARTS NORTH OF OFFICE BUILDING ARE IN VIOLATION OF 16-12 B3
ie IMPROPER MAINTENANCE OF ROOF FRAMING.
BOTH VIOLATIONS ABOVE NEED TO BE IMMEDIATELY ADDRESSED BY A QUALIFIED DESIGN PROFESSIONAL. BOTH THE CAR PARTS AND BREEZEWAY ARE SUBJECT TO IMMINENT COLLAPSE IN A HIGH WIND CONDITION.
03/08/2006 INITIAL CODE VIOLATION Approved IMC 2003
SEC. 502.7 -- APPLICATION OF FLAMMABLE FINISHES
502.7.3 -- SPRAYING AREAS - DOES NOT HAVE ANY
503.7.3.1 OPERATION SPACE HAS NO MECHANICAL VENTILATION
502.9.5 MIXING ROOM. FLAMMABLE AND COMBUSTIBLE LIQUIDS (PAINTS)
OCCUPANT REPAIRING SMALL DAMAGE TO VEHICLES. SMALL PAINT SPOT REPAIRS. LARGE JOBS ARE PAINTED OFFSITE WHERE PROPER BOOTH FACILITIES ARE AVAILABLE.
03/07/2006 INITIAL CODE VIOLATION Correction Required 1. RECEPTACLE AT ENTRY GATE EAST SIDE TO BE WEATHERPROOF.
2. SERVICE PANEL AT MAIN SERVICE NEEDS OPEN SLOTS COVERED AND DEAD FRONT OVER SCREWED.
3. WELDING OUTLET NOT ALLOWED INSIDE GARAGE AREA
NEC 2002, 511-7.
4. LIGHTING IN GARAGE AREA DOES NOT MEET NEC 2002 511-7(b) FOR A GARAGE, MUST BE 12' AFF OR TOTALLY ENCLOSED.
5. EXTENSION CORD USE NOT ALLOWED IN GARAGE WIRING FOR PERMANENT MEANS NEC 2002 400-8
6. JUNCTION BOXES UNDER COOLER TO BE MOVED OR MADE WEATHERPROOF
7. PAINT MIX ROOM ELECTRICAL INSUFFICIENT FOR MIXING AREA - MUST COMPLY WITH ELECT SECTION OF 2002-516
8. SPRAY BOOTH AREA DOES NOT MEET ELECTRICAL REQUIREMENTS FOR SPRAYING AS PER 576-2002 NEC
9. FLEX CONDUIT IMPROPERLY SUPPORTED THRU OUT GARAGE CEILING.
10. WIRING AT OUTSIDE HYDRAULIC LIFT, CORD FRAYED AT ENTRY TO BOX.
11. AC UNIT IN SPRAY AREA NOT ALLOWED.
12. GARAGE AREA RECEPTACLES SHOULD BE GFI PROTECTED 511.12
YOU SHOULD HAVE A QUALIFIED ELECTRICAL LICENSED CONTRACTOR REVIEW ITEMS AND REPAIR.
F.U. 30 DAYS