Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06PL02404
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* RECEIVED EXPANSION TANK INFORMATION |
|
02/21/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* SEE NOTE #2 FROM 2/8/07 EXPANSION TANK INFORMATION ON SITE. |
|
02/08/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL PROVIDE GAS FLEX THAT IS RATED FOR 270,000 BTU DEMAND OR HARD PIPE GAS TO BOILER 2) VENT FROM BOILER TO HAVE MINIMUM 1" CLEARANCE FROM COMBUSTIBLES WHEN DBL WALL 3) PROVIDE LISTING SHEET FOR EXPANSION TANK FOR COMPATABILITY FOR YOUR USE OR PROVIDE WESSEL'S PHONE NUMBER FOR CUSTOMER SERVICE ? SO WE CAN VERIFY |
|
02/07/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ACCESS AT 9:49 AM-PLEASE HAVE BILER ACCESS ON DAY OF REINSPECTION |
|
01/29/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE LISTING FOR EXPANSION TANK SHOWING THAT IS ASME RATED SEE NOTE #2 ABOVE |
|
12/29/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) 100 GALLON 270,000 BTU WATER HEATER IS A BOILER. SECURE AZ STATE BOILER PERMIT AND HAVE IT APPROVED. THEN RECALL 03090 SOT THE INSPECTOR CAN FINAL OUT THIS PERMIT 2) NOTE: BOILER REQUIRES ASME EXPANSION TANK |