Permit: T06PL02404

Parcel: 11601003E

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06PL02404

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/23/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED EXPANSION TANK INFORMATION
02/21/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SEE NOTE #2 FROM 2/8/07 EXPANSION TANK INFORMATION ON SITE.
02/08/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHALL PROVIDE GAS FLEX THAT IS RATED FOR 270,000 BTU DEMAND OR HARD PIPE GAS TO BOILER
2) VENT FROM BOILER TO HAVE MINIMUM 1" CLEARANCE FROM COMBUSTIBLES WHEN DBL WALL
3) PROVIDE LISTING SHEET FOR EXPANSION TANK FOR COMPATABILITY FOR YOUR USE OR PROVIDE WESSEL'S PHONE NUMBER FOR CUSTOMER SERVICE ? SO WE CAN VERIFY
02/07/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS AT 9:49 AM-PLEASE HAVE BILER ACCESS ON DAY OF REINSPECTION
01/29/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE LISTING FOR EXPANSION TANK SHOWING
THAT IS ASME RATED
SEE NOTE #2 ABOVE
12/29/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) 100 GALLON 270,000 BTU WATER HEATER IS A BOILER. SECURE AZ STATE BOILER PERMIT AND HAVE IT APPROVED. THEN RECALL 03090 SOT THE INSPECTOR CAN FINAL OUT THIS PERMIT
2) NOTE: BOILER REQUIRES ASME EXPANSION TANK