Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* GAS CARD AT METER SW GAS 889-1888 |
|
| 12/28/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SHALL HAVE NEW WATER HEATER ADDED TO PERMIT 2) SHALL PROVIDE SEDIMENT TRAP AT GAS ENTRY TO WATER HEATER 3) REMOVE TAPE AT SINGLE TO DBL WALL VENT CONNECTION TO WATER HEATER 4) PROVIDE BONDING OF BLDG GAS PIPING 5) PROVIDE DIELECTRIC PROTECTION ON HOT SIDE OF WATER HEATER |