Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2007 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 01/10/2007 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* PERMIT #T07PL00018 FOR WATER HEATER PULLED PLUMBING OK ELECTRICAL REQUIRES PERMIT & INSPECTION. 1. SHALL PROVIDE AIR TEST GAUGE IN 1/10 POUND INCREMENTS THAT IS FUNCTIONAL. 2. PROVIDE RATED FLEX FOR BTU REQUIREMENTS OF ROOFTOP UNIT. 3. PROVIDE ACCESS TO ROOFTOP FOR FUTURE INSPECTION. 4. PROVIDE SEDIMENT TRAP FOR ROOFTOP UNIT. 5. PIPING ON ROOF TO BE MINIMUM 3 1/2 ABOVE ROOF WITH CORRECT SUPPORTS. NOTE: FUTURE TEE CONNECTIONS REQUIRE A CITY APPROVED PLAN. SEE NOTES FROM 12/26/06 INSPECTION. |
|
| 12/26/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* WATER HEATER INSTALLED AFTER JULY 2006 INSTALLED WITHOUT PERMIT. NO EXPANSION TANK T&P RELIEF DRAIN NOT APPROVED WILL REQUIRE ELECTRICAL INSPECTION WIRING INCORRECT IT LOOKS LIKE YOU HAVE DONE A T.I WITHOUT PERMIT SINK DOES NOT MEET CODE WATER PIPING DOES NOT MEED CODE |