Permit: T06PL02376

Parcel: 133211280

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/26/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
12/22/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
AT LEAST TWO SECTIONS HAVE UNWRAPPED TOOL MARKS
REMOVE SHARP BURRS FROM UNISTRUT

AT FURNACE SINGLE WALL PIPE EXTENDS INTO ATTIC.
INSTALL DOUBLE WALL B VENT THRU CEILING
BOTH WH AND FURN VENTS ARE TOUCHING WOOD AT ROOF THIS IS A FIRE HAZARD!
PLUMBER SHALL PROVIDE 1" CLEARANCE FROM COMBUSTIBLES.
YOU MAY CALL FOR GAS AFTER CORRECTING
RECALL FOR FINAL INSPECTION.