Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* GAS WATER HEATER INSTALLED OK GAS PIPE OK PRESSURE TEST OK OK FOR GAS |
|
| 12/22/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/21/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEW WATER HEATER REQUIRES PERMIT 2. VENT SYSTEM NOT APPROVED 3. NO T&P RELIEF DRAIN 4. NO VALVE ON INLET 5. NO DRIP LEG ON GAS 6. REQUIRE AGA OR CSA APPROVED VALVE - INACCESSIBLE LOCATION. 7. BLACK IRON PIPE BELOW GRADE TO BE WRAPPED 8. REQUIRE 10 POUND TEST ON 30 POUND GAUGE |