Permit: T06PL02371

Parcel: 127050970


Addresses:

4723 E 2ND ST

Inspection Status: Partial Approval

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/22/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. GAS PIPING IS OK
2. BOND TO CW SIDE
3. THE WATER HEATER VENT DOES NOT HAVE PROPER CLEARANCE FROM COMBUSTIBLES - THIS IS A FIRE HAZARD
4. DOUBLE WALL B VENT IS REQUIRED OUTDOORS
5. PLUMBER SHALL MAKE CORRECTIONS BEFORE HAVING GAS RESTORED.
6. AFTER CORRECTIONS ARE MADE YOU MAY CALL FOR GAS SERVICE.
7. CLEARANCE TAG HAS BEEN LEFT
8. RECALL FOR FINAL INSPECTION.