Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/02/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 12/28/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 3/4" IS UNDERSIZED FOR FURNACE, WATER HEATER AND STOVE 2) 1/2" TO FURNACE IS UNDERSIZED 3) EXTEND 3/4" PIPING TO FURNACE SUPPLY FROM FULL SIZED 1" TEE 4) SUPPORT PIPING WITHOUT STRAIN 5) USE GALVANIZED 2 HOLE STRAPS NOT PLUMBERS TAPE 6) SECURE WATER HEATER VENT WITH SCREWS-NO TAPE AT DBL WALL 7) SEDIMENT TRAPS REQUIRED AT WATER HEATER AND FURNACE 8) HAVE AGA VALVES ON SITE |